dc.contributor.advisorLightstone, Marilyn-
dc.contributor.advisorCotton, James-
dc.contributor.authorHarris, Brianna-
dc.date.accessioned2024-07-16T19:41:53Z-
dc.date.available2024-07-16T19:41:53Z-
dc.date.issued2024-
dc.identifier.urihttp://hdl.handle.net/11375/29966-
dc.description.abstractThis thesis contributes an in-depth comparative study of u-tube and coaxial borehole heat exchangers. While it is widely accepted that the lower resistance of the coaxial heat exchanger should result in a performance advantage, the findings of several studies comparing the heat exchanger configurations did not definitively establish the mechanisms causing differences in performance. This study employs numerical modelling to consider heat exchangers over a broad range of time scales and under carefully controlled geometry and flow conditions, resulting in the identification of the key parameters influencing borehole heat exchanger performance. The first part of this study consists of a comparison of u-tube and coaxial heat exchangers under continuous loading. A detailed conjugate heat transfer numerical model was developed in OpenFOAM, designed to capture both short and long time scales of heat exchange, necessary to understand the nuanced differences between designs. A novel transient resistance analysis was employed to understand the dominant factors influencing performance. This study established that marginal differences exist between u-tube and coaxial borehole heat exchangers (BHEs) when operated continuously long term but that greater differences occur early in operation. The second phase of this investigation provided a framework for analysing borehole heat exchanger performance during intermittent operation, while also comparing u-tube and coaxial designs. During this study, it was found that reducing operating time, improving the the rate of the ground's recovery to its original temperature, and lowering the duty cycle improved BHE performance. Transit time was identified as a influential time scale, below which heating at the outlet was limited. Further, the benefits of operating below the transit time were mitigated by design-specific interaction between inlet and outlet flows. Finally, this study found that non-dimensionalizing operating time by transit time causes the differences between u-tube and coaxial performance to vanish, leading to the conclusion that differences in BHE performance are caused by variations in flow rather than thermal mass.en_US
dc.language.isoenen_US
dc.subjectBorehole heat exchangersen_US
dc.subjectComputational fluid dynamicsen_US
dc.subjectHeat transferen_US
dc.titleA numerical study of the short- and long-term heat transfer phenomena of borehole heat exchangersen_US
dc.typeThesisen_US
dc.contributor.departmentMechanical Engineeringen_US
dc.description.degreetypeThesisen_US
dc.description.degreeDoctor of Philosophy (PhD)en_US
dc.description.layabstractThis thesis provides an in-depth comparative study of two different designs of borehole heat exchanger, the u-tube and coaxial, which are used in geothermal applications to transfer heat to and from the ground. While many researchers anticipated that the coaxial design would perform better, several studies comparing the heat exchangers were not able to provide a clear answer about which heat exchanger performed best. This study addressed this gap by using detailed numerical simulations which showed that there was a marginal difference in performance between the two heat exchangers when operated for periods longer than a few hours, but that larger differences occurred early in operation (under 15 minutes). The results also showed that operating intermittently resulted in improvements in performance of the heat exchanger, particularly when operated for periods less than the time it takes fluid to travel the length of the piping.en_US
Appears in Collections:Open Access Dissertations and Theses

Files in This Item:
File Description SizeFormat 
Harris_Brianna_E_2024June_PhD.pdf
Open Access
2.62 MBAdobe PDFView/Open
Show simple item record Statistics


Items in MacSphere are protected by copyright, with all rights reserved, unless otherwise indicated.

Sherman Centre for Digital Scholarship     McMaster University Libraries
©2022 McMaster University, 1280 Main Street West, Hamilton, Ontario L8S 4L8 | 905-525-9140 | Contact Us | Terms of Use & Privacy Policy | Feedback

Report Accessibility Issue